RCD Safety Switch Requirements: AS/NZS 3000 Types A/B/F
Last updated on

RCD Safety Switch Requirements: AS/NZS 3000 Types A/B/F


Under AS/NZS 3000:2018 Clause 2.6.3.2.2, every final subcircuit in a domestic or residential installation — socket outlets, lighting and fixed equipment alike — requires RCD protection at 30mA or less, installed at the switchboard where the circuit originates. Amendment 2 later added a separate rule in Clause 2.6.2.2.2 that bans Type AC RCDs outright, and the wrong RCD type on a solar inverter or EV charger is now a documented CER audit failure point.

This guide covers what changed, which circuits need protection, which RCD type applies to each application, and what state regulators and auditors check on-site.


💸 What rebates can you claim this job?

Free Rebate Finder — current state and federal incentives for switchboard upgrades, solar, batteries and heat pumps, checked weekly against regulator sources.

Find Rebates →

What Changed: AS/NZS 3000:2018 and Amendment 2

AS/NZS 3000 is Australia and New Zealand's Wiring Rules standard — the foundational document governing electrical installation compliance. The 2018 edition replaced the 2007 edition, and Amendment 2 (published 30 April 2021) added the RCD type rules that now trip up solar and EV work.

Key changes from the 2018 edition and its amendments:

  1. Extended mandatory RCD coverage — the 2018 edition already required 30mA protection on all final subcircuits in domestic and residential installations, not just socket outlet circuits as the 2007 edition did
  2. Banned Type AC RCDs — Clause 2.6.2.2.2, inserted by Amendment 2, allowed a 24-month transition ending 30 April 2023, after which Type AC RCDs must not be installed in Australia
  3. Recommended Type A as the general type for installations, given the growth in electronics, renewables and DC waveforms on the AC supply
  4. Clarified the alteration trigger — Clause 2.6.3.2.5 requires RCD protection on circuits affected by alterations or a switchboard replacement

The practical effect: jobs that were compliant under AS/NZS 3000:2007 may not comply with the current standard, and a Type AC device on the shelf is no longer installable. Every switchboard upgrade and solar installation must be assessed against the 2018 edition with Amendment 2.


Which Circuits Require RCD Protection

Residential Dwellings

Under AS/NZS 3000:2018 Clause 2.6.3.2.2, every final subcircuit in a domestic or residential installation requires RCD protection at ≤30mA — there is no longer a socket-outlets-only rule:

Circuit TypeRCD Required?Notes
Socket outlet circuits (all)YesAll final sub-circuits supplying socket outlets
Lighting circuitsYesRequired since the 2018 edition, not just Amd 2
Outdoor circuitsYesAny circuit with external socket outlets
Bathroom/laundry circuitsYesIncludes shaver outlets
Kitchen circuitsYesIncluding fixed appliance circuits
Garage/carport socket outletsYesTreated as outdoor circuits
Fixed equipment (ovens, hot water, air conditioning)YesCovered as final subcircuits in a dwelling

What does not require RCD protection in residential: narrower than most guides suggest. The 2018 residential rule is written as an all-final-subcircuit requirement, so there is no general exemption list to work from — only the specific cases the standard carves out where RCD operation would itself create a hazard greater than the shock risk (some safety-service and emergency-lighting arrangements), and those are a documented design decision, not a default. "It's hard-wired, so it doesn't need one" is not an exemption under the wiring rules. The rental minimum standards are where that logic comes from — Victoria's covers power and lighting circuits but not fixed cooking, hot water or air-conditioning where the board already has circuit breakers, and Queensland's applies to power point circuits only — and neither instrument overrides AS/NZS 3000 on new work.

Commercial and Industrial

The commercial rule is narrower than the residential one, and it is the one most often over-applied. Clause 2.6.3.2.3.3 requires 30mA RCD protection on final subcircuits rated at 32A or less in a non-domestic installation where they supply:

  • socket outlets (single or three phase)
  • lighting
  • directly connected hand-held equipment
  • directly connected equipment that represents an increased risk of electric shock

Everything above 32A, and fixed equipment not in one of those categories, is not caught by that clause — it is assessed by the designer against the nature of the load and the risk. Other triggers that sit alongside it:

  • Construction and demolition sites (AS/NZS 3012): every circuit supplying portable tools and temporary supplies needs RCD protection — a separate standard to AS/NZS 3000
  • Healthcare facilities: patient-area requirements, including medical isolation transformers, are in AS/NZS 3003
  • Swimming pools and spas: Clause 6.3 sets the zones (0, 1 and 2), the supplementary equipotential bonding and the RCD requirements, with Table 6.2 carrying the installation detail. The pool figures were renumbered by the 2018 edition itself (Figures 6.5, 6.6, 6.8 and 6.11), not by Amendment 2 — so check which edition an older reference was written against
  • Baths and showers: Amendment 2 rewrote Clause 6.2.4.1 and Table 6.1 — Zone 0 now IPX7, Zones 1 and 2 IPX4, Zone 3 no specific degree of protection — and deleted the IPX5 footnote for communal baths and showers. Degree-of-protection references written against the original 2018 text no longer line up
  • Marinas, generating systems, hazardous areas: Section 7 (special electrical installations)

RCD Types: Which Application Requires What

This is where most compliance failures occur. Specifying the wrong RCD type creates an audit fail regardless of whether an RCD is installed at all.

Type AC Detects sinusoidal AC fault currents only. Type AC RCDs must not be installed in Australia — Clause 2.6.2.2.2 (Amendment 2) ended the transition period on 30 April 2023. Existing Type AC devices may stay in place if they test correctly, but they cannot be fitted to new work, new final subcircuits, or as a like-for-like replacement.

On any circuit serving a solar inverter, EV charger or variable-speed drive, Type AC is not just unsuitable — it is unlawful to install.

Type A Detects sinusoidal AC and pulsating DC fault currents. This is the general type recommended by Amendment 2 and the default for:

  • Single-phase solar inverters (grid-connect) — unless the inverter manual specifies Type B
  • Most modern appliance circuits with switch-mode power supplies
  • General residential circuits where electronics are connected

Type A is now the practical baseline for residential work, and it is the sensible replacement for an existing Type AC device — but it is not the only lawful one. Type A, Type F and Type B may all be installed; the governing test is whether the type detects the fault waveform the load can produce. Replacing a Type AC device with a Type A is the usual answer; the answer changes where the equipment manual or the inverter's requirements call for something else.

Type F Detects sinusoidal AC, pulsating DC, and high-frequency leakage currents from variable-frequency drives. Required for:

  • Air handling units with VFD-controlled fans
  • Industrial machinery with variable-speed motor drives
  • Some HVAC systems

Type F is uncommon in residential but increasingly relevant in commercial electrical work.

Type B Detects all fault current types including smooth DC up to several kHz. Required where there is no other DC fault-current detection:

  • EV chargers (EVSE) without a built-in 6mA RDC-DD
  • Three-phase solar inverters where the manufacturer specifies Type B
  • Battery storage systems with DC-connected inverters
  • Any load with a rectifier bridge producing smooth DC output
ApplicationMinimum RCD Type
Standard socket outlets (residential)Type A
Lighting circuitsType A
Single-phase solar inverterType A (check inverter specs — may require Type B)
Three-phase solar inverterType B where specified by the manufacturer
Battery storage (DC-coupled)Type B where specified by the manufacturer
EV charger with integrated 6mA RDC-DDType A
EV charger without DC fault detectionType B
Variable frequency drivesType F or Type B

Practical rule: the equipment manual decides the type. Specifying a higher type than the manual requires adds cost without compliance benefit; specifying a lower one is a non-compliance and, on solar and battery work, the thing auditors look for first.


Switchboard Upgrades: When Does Full Retrofitting Apply?

This is the grey area that generates the most compliance questions.

Full switchboard replacement: Installing a new switchboard — removing the old board and fitting a new one — triggers full compliance with AS/NZS 3000:2018 on all circuits connected to that board. Every final sub-circuit must receive RCD protection compliant with the current standard.

Adding new circuits to an existing board: The new circuit must comply with AS/NZS 3000:2018, and Clause 2.6.3.2.5 requires RCD protection on any circuit that is altered or whose source of supply changes. Existing untouched circuits on the board are not automatically required to be upgraded.

Where the line sits in practice:

  • Adding 1–2 new circuits: the new circuits need RCD protection; the rest of the board does not automatically
  • Replacing the main switch, upgrading the incomer, or replacing all circuit protection on the board: Clause 2.6.3.2.5 treats this as triggering RCD protection for the final subcircuits supplied by that board
  • Adding solar or a battery that back-feeds existing circuits: those circuits are "altered" because their source of supply has changed, so they need RCD protection

Energy Safe Victoria's published position: ESV's guidance on multiple-mode inverters and battery systems states that circuits connected to an alternative supply are deemed altered for the purposes of AS/NZS 3000, so Clause 2.6.3.2.5 applies and suitable RCD protection is required on those circuits — including the correct RCD type specified by the inverter manufacturer.

When uncertain, apply the current standard to the entire board. The cost of an RCD-per-circuit retrofit is orders of magnitude less than a failed inspection and remediation.


State Variations in Enforcement

Victoria (Energy Safe Victoria) ESV is the most active enforcer of AS/NZS 3000 technical requirements in Australia. Amendment 2 requirements have been incorporated into ESV's compliance framework, and its electrical inspection and audit teams check RCD type compliance specifically on solar and battery installations.

Victoria's rental mandate is the broadest in the country, but it is not the only one. Queensland requires an approved safety switch on every power point circuit within 90 days of a tenancy starting — or of taking possession — under sections 28 and 29 of the Electrical Safety Regulation 2026, with a maximum penalty of 15 penalty units, which is $2,590 at the 2026–27 Queensland penalty unit value of $172.70. Note that the Electrical Safety Office's own rental-property page still quotes "up to $1,500", which predates the current penalty unit value and understates the maximum. Western Australia requires at least two RCDs protecting all power and lighting circuits on the switchboard before a property can be leased, enforced under the Electricity Regulations 1947 (up to $15,000 for an individual, $100,000 for a body corporate). What is unique to Victoria is the scope plus the recurring check. Under the rental minimum standards, the electrical safety standard commenced 29 March 2023: every power outlet circuit and every lighting circuit in a rented premises must be protected by a switchboard-type circuit breaker and a switchboard-type RCD (or RCBO). The practical trap is the wording — where the board already has circuit breakers, the electrician can add RCD protection to the power and lighting circuits without touching fixed cooking, hot water or air-conditioning circuits; where it is an old fuse board, the whole switchboard must be replaced and every circuit, fixed equipment included, must have circuit breaker components. Rental providers must also have an AS/NZS 3019 electrical safety check every two years, which is recurring inspection work most electricians never quote for.

NSW (Building Commission NSW) Building Commission NSW administers the CCEW (Certificate of Compliance for Electrical Work) through BCNSW eCert — the certificate must be lodged there, not held as a PDF. A CCEW is the certifying electrician's declaration that the work meets AS/NZS 3000, so a certificate issued on non-compliant work is the exposure under the Gas and Electricity (Consumer Safety) Act 2017. Audit is the mechanism: BCNSW audits certificated work against the standard and can require rectification by written direction notice.

Queensland (Electrical Safety Office) ESO Queensland requires all electrical work to comply with the current edition of AS/NZS 3000. The ESO's audit program has specifically focused on solar installations with incorrect RCD types. Queensland does not use a "Form" for electrical compliance: the contractor must issue a certificate of testing and compliance for electrical installation work, and a certificate of testing and safety for work on electrical equipment, under the Electrical Safety Regulation — and keep a copy for five years.


Testing Requirements: AS/NZS 3017

Installed RCDs must be tested for correct operation — Clause 8.3.10 of AS/NZS 3000 requires this for newly installed devices, and the test methods sit in AS/NZS 3017 — Electrical Installations: Verification Guidelines. Amendment 2 also added Clause 8.3.2.2, which recommends recording test results that produce a value rather than leaving them undocumented.

Required tests per RCD:

  1. Trip time test: Apply 1× rated residual current (30mA on a 30mA device) — it must operate within 300 ms — then at 5× rated current, where the limit is 40 ms. Time-delayed (S-type) RCDs and some Type F and Type B devices run on their own curves, so check the device data rather than assuming the generic limits.
  2. Ramp test: Apply increasing current until trip — confirms the trip threshold matches the rating.
  3. Test button verification: Manual test button must operate correctly.

Documentation required:

  • Measured trip time for each RCD
  • Test instrument model and calibration date
  • Circuit identification
  • Technician name and licence number

CER auditors and state regulator inspectors increasingly check for RCD test records as part of site compliance verification for solar and battery installations. Undocumented RCDs — even correctly installed ones — create a compliance gap.


How ServiceM8 Supports Compliance Documentation

Maintaining RCD test records, linking them to job files, and retrieving them for audits is where paper-based systems fall apart. ServiceM8 lets you:

  • Attach RCD test results, photos and certificates to the job record so the evidence sits with the work
  • Build a custom form for RCD testing with the fields you actually use — on the Growing plan ($79/mo); the custom form builder is not on Free or Starter ($29), which only complete forms bought from the Form Store
  • Set recurring jobs for periodic RCD testing and the two-yearly AS/NZS 3019 inspection on maintenance contracts
  • Attach the certificate number and issue date to the job so the paperwork is traceable at audit

What it does not do: it does not generate or lodge a CCEW, a certificate of testing and compliance or any other statutory certificate. NSW lodgement goes through BCNSW eCert (or the approved API for eligible high-volume contractors), Queensland certificates are issued under the ES Regulation, and Victoria's COES is lodged with ESV — a form builder is a record, not a lodged certificate. Keep that distinction straight before promising a client a paperless close-out.

Start your free ServiceM8 trial →

FAQ

Which circuits require RCD protection under AS/NZS 3000:2018?

Every final subcircuit in a domestic or residential installation — socket outlets, lighting and fixed equipment such as ovens, hot water and air conditioning — under Clause 2.6.3.2.2. This has been the rule since the 2018 edition replaced the 2007 edition, which only covered socket outlet circuits. Amendment 2 added the Type AC ban, not the lighting coverage.

What RCD type do I need for a solar inverter installation?

Type A as the general choice for single-phase inverters, unless the inverter manual specifies Type B — in which case the manufacturer's requirement governs and Type A is a non-compliance. Always check the installation manual before specifying.

What RCD type is required for an EV charger?

Either a Type B RCD, or a Type A RCD with a 6mA RDC-DD (built into most Mode 3 chargers to IEC 62955). Type AC is prohibited. Confirm with both the charger's installation documentation and your DNSP's technical standards.

Does replacing a switchboard trigger full RCD compliance on all circuits?

Yes. A full switchboard replacement triggers RCD protection under Clause 2.6.3.2.5 for all final subcircuits supplied by that board. Adding circuits to an existing board requires the new or altered circuits to comply; untouched circuits are not automatically upgraded.

What does "substantially altered" mean under AS/NZS 3000?

The standard does not use that phrase — it talks about alterations to an installation and replacement of switchboards (Clauses 2.6.3.2.5 and 1.4.8). What matters is whether a circuit has been altered or had its source of supply changed. When uncertain, apply the current standard to the whole board.